IDC cabinet
Specifications:
1. Cabinet Size: 47U
2. PDU Specifications:
1) Input voltage: 346-415VAC
2) Input current: 3 x 60A
3) Output voltage: 200~240VAC
4) Outlets: 36 ports of C39 sockets with self-locking feature Socket compatible to both C13 and C19
5) Protection: 12 pcs of 1P 20A UL489 hydraulic magnetic circuit breakers One breaker every three outlets
6) Remote monitor PDU input current, voltage, power, KWH
7) Remote monitor each output port’s current, voltage, power, KWH
8) Smart Meter with Ethernet/RS485 interface, support HTTP/SNMP/SSH2/MODBUS
9) UL/cUL Listed and Certified (ETL Mark)
3. Two PDUs installed vertically on both sides of the cabinet.
4. Two 5*6AWG cables with CEE 63A plug
-
36 PORTS P14&8 PORTS C19 BASIC RACK PDU
PDU Specifications:
1. Input Voltage: three phase 346~480V
2. Input Current: 2*(3*125A)
3. Output voltage:single-phase 200~277V
4. Outlet: 36 ports of 4-pin PA45 (P14) Sockets 8 ports of C19 Sockets
5. Two port Integrated 125A main circuit breaker (UTS150HT FTU 125A 3P UL)
6. Each port has 1P 277V 20A UL489 Hydraulic Magnetic circuit breake
-
40 PORTS C19 BASIC RACK PDU
PDU Specifications:
1. Input Voltage: three phase 346~480V
2. Input Current: 3*250A
3. Output voltage:single-phase 200~277V
4. Outlet: 40 ports of C19 Sockets organized in three sections
5. Each port has 1P 20A circuit breaker
-
18 PORTS C19&2 PORTS C13 BASIC PDU
PDU Specifications:
1. Input Voltage: three phase 346~415V
2. Input Current: 2 sets of 3*60A, one from each side of PDU
3. Output voltage: single-phase 200~240V
4. Outlet: 18 self-locking C19 Sockets (20A Max) 2 self-locking C13 Sockets (15A Max)
5. 6 pcs 1P 60A UL489 breakers, each protects 3 sockets
6. Two port C13 for network switches
7. Powder coating : Pantone Black
-
Miner Rack with 36 Ports PA45&8 Ports C19 PDU
Specifications:
1. Cabinet Size(W*H*D):1020*2280*560mm
2. PDU Size(W*H*D):120*2280*200mm
Input Voltage: three phase 346~480V
Input Current: 2*(3*125A)
Output voltage:single-phase 200~277V
Outlet: 36 ports of 4-pin PA45 (P14) Sockets 8 ports of C19 Sockets
Two port Integrated 125A main circuit breaker (UTS150HT FTU 125A 3P UL)
Each port has 1P 277V 20A UL489 Hydraulic Magnetic circuit breaker
-
CEE 63A Male Plug TO Open Power Cable
CEE 63A male plug Power Cable:
Cable material: UL 2586 6AWG*5C, UL certified;
Male plug: (3P+N+PE):
Rated current: 63A
Rated voltage: 480V
Number of poles: 5P
Clock position: 7h
Termination: Screw
Protection Type: IP67
Certification: CE
Standard: IEC 60309
Application: HPC Data Center.
-
CEE 125A Male Plug TO Open Power Cable
CEE 125A male plug Power Cable:
Cable material: UL 2586 1AWG*5C, UL certified;
Male plug: (3P+N+PE):
Rated current: 125A
Rated voltage: 480V
Number of poles: 5P
Clock position: 7h
Termination: Screw
Protection Type: IP67
Certification: CE
Standard: IEC 60309
Application: HPC Data Center.
-
IDC Rack (Internet Data Center Rack)
Key Features & Specifications:
Size: standard width: 19 inches (482.6 mm) Height: Rack Unit 47U Depth: 1100mm
Support custom size according to your requirements.
Load Capacity: Rated in kilograms or pounds. It’s crucial to ensure the cabinet can support the total weight of all installed equipment.
Construction Material: Made from heavy-duty, cold-rolled steel for strength and durability.
Perforation: Front and rear doors are often perforated (meshed) to allow for optimal airflow.
Compatibility: Designed to hold standard 19-inch rack-mount equipment.
Cable Management: Two input cables with CEE 63A plugs, cable management bars / finger ducts to organize and guide network and power cables.
Efficient Cooling: Perforated doors and panels facilitate proper airflow, allowing conditioned cold air from the data center’s cooling system to flow through the equipment and exhaust hot air effectively, preventing overheating.
Vertical PDU (Power Distribution Unit): Two 36 ports C39 smart PDUs mounted on the vertical rails to provide power outlets close to the equipment.
Application: IDC Cabinet, also known as a ”Server Rack” or ”Network Cabinet”, is a standardized, enclosed frame structure designed to securely house and organize critical IT equipment within a Data Center or dedicated server room. “IDC” stands for ”Internet Data Center”.
-
CEE 63A female connector TO 63A male plug power cable
CEE 63A female&male connectors Power Cable:
Cable material: UL 2586 6AWG*5C, UL certified;
Female connector (3P+N+PE):
Rated current: 63A
Rated voltage: 480V
Number of poles: 5P
Clock position: 7h
Male plug: (3P+N+PE):
Rated current: 63A
Rated voltage: 415V
Number of poles: 5P
Clock position: 6h
Termination: Screw
Protection Type: IP67
Certification: CE
Standard: IEC 60309
Application: HPC Data Center.
-
NEMA 6-50 TO PA45 Power Cable
6-50 TO PA45 4-pin Power Cable
Cable material: UL SOO 10AWG*3C 105℃ 600V
Connector A: PA45 plug: ANEN PA45 4-pin connectors composition, rated 50A, 600V, UL certified
Connector B: 6-50 plug: rated 50A, 250V
Application: Immersion cooling system.
-
CEE 125A female connector TO 125A male plug power cable
CEE 125A female&male connectors Power Cable:
Cable material: UL 2586 1AWG*5C, UL certified;
Female connector (3P+N+PE):
Rated current: 125A
Rated voltage: 480V
Number of poles: 5P
Clock position: 7h
Male plug: (3P+N+PE):
Rated current: 125A
Rated voltage: 415V
Number of poles: 5P
Clock position: 6h
Termination: Screw
Protection Type: IP67
Certification: CE
Standard: IEC 60309
Application: HPC Data Center.
-
NEMA L6-15R TO C20 Power Cable
POWER CORD – 15 AMP NEMA L6-15R TO IEC C20 Plug CABLE
Cable material: UL SJT 14AWG*3C 105℃ 300V
Connector A: NEMA L6-15R, rated 15A, 250V, UL certified
Connector B: IEC C20 plug, rated 20A, 250V, UL certified