PDUs
-
HPC 24 PORTS C39 SMART PDU-125A
PDU Specifications:
1. Input voltage: 346-415V
2. Input current: 3*125A
3. Output voltage: 200-240V
4. Outlets: 24 ports of C39 sockets with self-locking feature Socket compatible to both C13 and C19
5. Protection: 24pcs of 1P20A UL489 hydraulic magnetic circuit breakers One breaker for every one outlet
6. Remote monitor PDU input and each port current, voltage, power, KWH
7. Remote monitor each output port’s current, voltage, power, KWH
8. Smart Meter with Ethernet/RS485 interface, support HTTP/SNMP/SSH2/MODBUS
9. UL/CSA Certified (ETL Mark)
-
16 PORTS C13 SMART PDU
PDU Specifications:
1. Input Voltage: single-phase 200~240V
2. Input Current: 24A, 50/60Hz
3. Output voltage: single-phase 200~240V
4. Outlet Sockets: 16 ports of C13 outlets (8 in Section A, 8 in Section B)
5. Output Current: 10A Per C13, 16A MAX Per Section, 24A Max Total
6. Each Section is protected by a UL489 2P 20A circuit breaker
7. Remote monitor and control ON/OFF of each port
8. Remote monitor input and per port current, voltage, power, power factor, KWH
9. Onboard LCD display with menu control
10. Ethernet/RS485 interface, support HTTP/SNMP/SSH2/MODBUS
11. Powder Coating color: RAL900
-
L16-30R 10 PORTS SMART PDU
PDU Specifications:
1. Input voltage: 3-phase 346-480VAC
2. Input current: 3 x 250A
3. Output voltage: 3-phase 346-480 VAC
4. Outlet: 10 ports of L16-30R Sockets
5. Each port has Noark UL489 3P 30A circuit breaker
6. Remote monitor and control ON/OFF of each port
7. Remote monitor input and per port current, voltage, power, power factor, KWH
8. Onboard LCD display with menu control
9. Ethernet/RS485 interface, support HTTP/SNMP/SSH2/MODBUS
10. Intemal fan with LED indicator
11. Powder coating : Pantone Black
-
SA2-30 21 Ports Smart PDU
SA2-30 Specifications:
1. Input Voltage: three phase 346~480V
2. Input Current: 3 x 250A
3. Output Voltage: three-phase 346-480V
4. Outlet: 21 ports of 4-pin SA2-30 sockets
5. Each port has Noark 3P 20A circuit breaker
6. LED Indicator for each port
7. Three full length copper busbars for L1/L2/L3
8. Remote monitor and control ON/OFF of each port
9. Remote monitor input and per port current, voltage, power, PF, KWH
10. Onboard LCD display with menu control
11. Ethernet/RS485 interface, support HTTP/SNMP/SSH2/MODBUS
-
SA2-30 20 Ports Smart PDU – For Immersion Cooling
SA2-30 Specifications:
1. Input Voltage: three phase 346~480V
2. Input Current: 3 x 250A
3. Output Voltage: three-phase 346-480V
4. Outlet: 20 ports of 4-pin SA2-30 sockets
5. Each port has Noark UL489 3P 20A circuit breaker
6. One C13 port with 1P 2A circuit breaker
7. LED Indicator for each port
8. Front cover can be opened in sections for maintenance
9. Remote monitor and control ON/OFF of each port
10. Remote monitor input and per port current, voltage, power, PF, KWH
11. Onboard LCD display with menu control
12. Ethernet/RS485 interface, support HTTP/SNMP/SSH2/MODBUS
-
SA2-30 12 Ports Basic PDU
SA2-30 Specifications:
1. Input voltage: 3-phase 346-415 VAC
2. Input current: 3 x 80A
3. Output voltage: single-phase 200-240VAC
4. Outlet: 12 ports of SA2-30 sockets
5. Each port has 1P 20A circuit breaker
-
L7-20R 18 Ports Smart PDU
L7-20R Specifications:
1. Input Voltage: three-phase 346-480V
2. Input Current: 3 x 125A
3. Output voltage: single-phase 200-277V
4. Outlet: 18 ports of L7-20R sockets
5. Each port has 1P 20A circuit breaker
6. Remote monitor and control ON/OFF of each port
7. Remote monitor input current, voltage, power, power factor, KWH
8. Onboard LCD display with menu control
9. Ethernet/RS485 interface, support HTTP/SNMP/SSH2/MODBUS
-
L16-30R 10 Ports Basic PDU – Receptacles face downward
L16-30R Specifications:
1. Input voltage: 3-phase 346-480VAC
2. Input current: 3 x 250A
3. Output voltage: 3-phase 346-480 VAC
4. Outlet: 10 ports of L16-30R Sockets
5. Each port has Noark UL489 3P 30A circuit breaker
-
HPC 24 Ports C39 SMART PDU – 60A
HPC C39 Specifications:
1. Input: 346~415V, 3 x 60A
2. Output: 200~240VAC
3. Outlets: 24 ports of C39 sockets with self-locking feature, compatible with C13 and C19
4. Output phase rotation ABCABC in black, red, blue
5. Protection: each TWO ports have 1P 20A UL489 hydraulic magnetic circuit breaker
6. Remote monitor PDU input and each port current voltage, power, KWH
7. Smart meter with Ethernet/RS485 interface, support HTTP/SNMP/SSH2/MODBUS
8. Onboard LCD display with menu control and local monitoring
9. Ambient temperature up to 60°C
10. Input cable 5*6AWG, 3 meters
-
PA45 28 PORTS SMART PDU
PDU Specifications:
1. Input Voltage: three-phase 346-480V
2. Input Current: 4*400A
3. Output voltage: 3-phase 346-480V or single-phase 200-277V
4. Outlet: 28 ports of 6-pin P34 sockets
5. PDU is compatible with T21 and S21 miners
6. Each port has Noark 3P 30A B1H3C30 circuit breaker
7. Sockets and circuit breakers can be serviced without opening front cover
8. Onboard LCD display with menu control
9. Ethernet/RS485 interface, support HTTP/SNMPISSH2/MODBUS/CA
10. Internal fan with LED indicator
11. Dual input lugs (YA272N type) on the front and back of busbar and through bolted
-
PA45 21 PORTS SMART PDU
PDU Specifications:
1. Input voltage: 3-phase 346-480 VAC
2. Input current: 3 x 150A
3. Output voltage: 3-phase 346-480 VAC or single-phase 200-277 VAC
4. Outlet: 21 ports of 6-pin P34 sockets
5. PDU is compatible with T21 and S21 miners
6. Each port has 3P 25A circuit breaker
7. Remote monitor and control ON/OFF of each port
8. Remote monitor input and each port’s current, voltage, power, power factor, KWH
9. Onboard LCD display with menu control
10. Ethernet/RS485/USB interface, support HTTP/SNMP/SSH2/MODBUS/CA
11. Sockets can be replaced without opening PDU top cover
12. PDU can be connected to plug and play temp/humidity or other sensors via USB
-
PA45 36 Ports Smart PDU with main breaker
PDU Specifications:
1. Input voltage: 3-phase 346-480 V
2. Input current: 3 x 250A
3. Output voltage: 3-phase 346-480 V or single-phase 200-277 V
4. Outlet: 36 ports of 6-pin P34 sockets
5. Integrated 250A main circuit breaker
6. Each port has 3P 25A circuit breaker
7. PDU is compatible with T21 and S21 miners
8. Remote monitor and control ON/OFF of each port
9. Remote monitor input and each port’s current, voltage, power, power factor, KWH
10. Onboard LCD display with menu control
11. Ethernet/RS485 interface, support HTTP/SNMP/SSH2/MODBUS/CA
12. Internal fan with LED indicator